PID Chap. 3 - PID Algorithm | |||||||||||||||||||
|
The PID algorithmController ActionPROCESS ACTION Defines the relationship between changes in the valve and changes in the measurement. DIRECT Increase in valve position causes an increase in the measurement. REVERSE Increase in valve position causes a decrease in the measurement.
CONTROLLER ACTION Defines the relationship between changes in the measured variable and changes in the controller output. DIRECT Increase in measured variable causes an increase in the output. REVERSE Increase in measured variable causes a decrease in the output.
The controller action must be the opposite of the process action. Auto/Manual Manual Mode: The operator adjust the output to operate the plant. During startup, this mode is normally used.
Automatic Mode: The control algorithm manipulates the output to hold the process measurements at their setpoints.
This should be the most common mode for normal operation. Key concepts The PID control algorithm does not "know" the correct output to bring the process to the setpoint.
The PID algorithm must be "tuned" for the particular process loop. Without such tuning, it will not be able to function.
The PID Control Algorithm The PID control algorithm comprises three elements:
The algorithm is normally available in several combinations of these elements:
We will examine each of the three elements below: Proportional E = Measurement - Setpoint (direct action) E = Setpoint - Measurement (reverse action) Output = E * G + k
The output is equal to the error times the gain plus the manual reset. If the manual reset stays constant, there is a fixed relationship between the setpoint, the measurement, and the output. Proportionalunits The proportional or gain term may be calibrated in two ways: Gain and Proportional Band Gain = Output/Input Increasing the gain will cause the output to move more. Proportional band is the % change in the input which would result in a 100% change in the output. Proportional Band = 100/Gain We will use gain in this document. ProportionalOutput vs. Measurement
Proportional only control produces an offset. Only the adjustment of the manual reset removes the offset.
ProportionalOffset Offset can be reduced by increasing gain.
Proportional control with low gain
Proportional control with higher gain ProportionalReducing offset with manual reset Offset can be eliminated by changing manual reset.
Proportional control different manual reset Adding automatic reset With proportional only control, the operator "resets" the controller (to remove offset) by adjusting the manual reset:
This manual reset may be replaced by automatic reset which continues to move the output whenever there is any error:
This is called "Reset" or Integral Action. Note the use of the positive feedback loop to perform integration. Reset or integral mode Reset Contribution: Out = g X Kr X integral of error where g is gain, Kr is the reset setting in repeats per minute.
Units used to set integral or reset Assume a controller with proportional and integral only. Calculation of repeat time: (gain and reset terms used in controller) With the error set to zero (measurement input = setpoint), make a change in the input and note the immediate change in output. The output will continue to change (it is integrating the error). Note the time it takes the output to, due to the integral action, repeat the initial change made by the gain action.
Some control vendors measure reset by repeat time in minutes. This is the time it takes the reset (or integral) element to repeat the action of the proportional element. Others measure reset by "repeats per minute". Repeats per minute is the inverse of minutes of repeat This document will use repeats per minute. Derivative First used as a part of a temperature transmitter ("Speed-Act" - Taylor Instrument Companies) to overcome lag in transmitter measurement. Also known as Pre-Act and Rate. Derivative Contribution: Out = g x Kd x de/dt where g is gain, Kd is the derivative setting in minutes.
Response of controller with proportional and derivative:
The amount of time that the derivative action advances the output is known as the "derivative time" measured in minutes. All major vendors measure derivative (Derivative, Rate) the same. Complete PID response Non-Interactive (text book) form:
Out = G (e + R+ D )Where G = Gain R = Reset (repeats per minute) D = Derivative (minutes) Note: See Interactive vs. Noninteractive (below) back to index go to chapter 2: the control loop |
||||||||||||||||||
| ControlSim The PID controller and process simulator based on MS Excel spread sheets. $45.00 | Click here to get more details, buy, and download |
Buy and download my eBook: The
PID Control Algorithm: How It Works, How To Tune It, and How to Use It. 2nd ed.
62pp |
Get more details, buy, and download |
Thousand Acre Swamp Hike Schedule
A schedule of the 2006 public hikes at Thousand Acre Swamp in Penfield, NY